Equipment technical parameters

Technical requirements for 2 ton intermediate frequency furnace rectifier transformer

Date:2019-07-26 Click:

Technical requirements for 2 ton intermediate frequency furnace rectifier transformer

1, capacity: 1900KVA

2. Primary voltage: 10KV; secondary voltage: 660V

3, short circuit impedance: 6-8%

4. There is a manual no-load voltage regulating switch on the high voltage side (the output voltage can be adjusted in -5%, 0, +5%)

5, connection method: Δ / Δ-Y